Corrosion Inhibitor for Cooling Water Systems having unique formulation with highly concentrated liquid cooling water treatment compound with indicator, ferrous & Non ferrous corrosion inhibitors, antiscalants , dispersant and buffer solution of non carbonate.
Prolongs the life of equipment by keeping it scale and corrosion free. Since RXSOL-40-4001-025 is alkaline, it will
suppress acid corrosion, which would otherwise result in sever pittings. It improves cooling
	efficiency by maintaining clean heat transfer surfaces , from Radiators, DG - sets, Closed Cooling and chiller System.
	
	Before testing of Nitrite level, Here is some point and guideline,  what you need to do. : 1 take the following readings; pH, TDS (uS), and nitrite level.and record. 2 add the Chemical your are using. 3. wait for a period of time for the sysem to circulate. 
	for a period of time.
	
	If the TDS and Nitrite drop you have a leak/ unknown makeup. if the TDS stays stable and the nitrite drops you have a biological problem. Bacteria that convert nitrite to nitrate.
	
	Solution ::: Use DI water in place of general water, And also use. Algaecide to control Bacterial growth inside water system ... http://rxmarine.com/Biocide-
	 
Refer to technical datasheet.
GENERAL RECOMMENDATION :
| Nitrite (as PPM NO2) | 0 | 100-200 | 300-600 | 700-900 | 1100-1300 | 
| RXSOL-40-4033-025 / 1000L | 13.0 | 11.3 | 8-10 | 5-7 | 1.5-3.5 | 
NOTE ::: -- If nitrite level becomes 1440-2400 then doses should be ZERO.
Initial dosage for an untreated system is 9 litres of RXSOL-40-4001-025 / 1000 litres of untreated distilled water. This will bring the treatment up to the minimum level of 1000 ppm nitrite. For best result and prolonged engine life add RXSOL-40-4001-025 every 500 -6500 km. or 250 to 300 hours of running time or every 2 month interval. Specially designed for use in water systems of internal combustion equipment. pH should be maintained between 8.3 and 10 by the treatment.